Steam-heated heat exchangers transfer thermal energy from steam to water or another process fluid through a...
Tank Heating Load Calculation: Start-up, Heat Losses and Steam Demand
Heating liquids in tanks is a common requirement across process industries. Tank heat-load calculations should not be limited to the energy needed to raise liquid temperature. Depending on the application, vessel heating, wall losses, exposed-surface losses and cold articles introduced into the process may also be important.
A key distinction is the difference between start-up load and operating load.
Closed and open tanks
Totally enclosed, well-insulated tanks generally have a simpler heat balance. Open-topped tanks can have substantial losses from the exposed liquid surface and may receive cold articles or materials.
Typical applications and temperatures
| Application | Typical temperature |
|---|---|
| Boiler feedtank | 80–90°C |
| Hot-water tank | 40–85°C |
| Degreasing tank | 90–95°C |
| Metal treatment / plating | 70–85°C |
| Rust or scale removal | 90–95°C |
| Raw-juice heating | 80–85°C |
| Pharmaceutical wash tank | about 70°C |
| Caustic-oil heating | about 140°C |
| Heavy fuel oil for pumping | 30–40°C |
Components of total heat demand
- Heating the process liquid.
- Heating the vessel material.
- Heat loss from solid vessel surfaces.
- Heat loss from the exposed liquid surface.
- Heat absorbed by cold articles or materials.
Heating liquid, vessel and articles
Q̇ = m · cp · ΔT / t
Heat loss from vessel walls
Q̇ = U · A · ΔT
Where a tank bottom lies flat on the ground and is not exposed to ambient air, its corresponding loss may normally be neglected in this type of calculation.
Effect of insulation
- 25 mm insulation: multiply U by 0.2.
- 50 mm insulation: multiply U by 0.1.
Effect of air movement
| Air velocity | Multiplying factor |
|---|---|
| 0 m/s | 1.0 |
| 0.5 m/s | 1.3 |
| 1.0 m/s | 1.7 |
| 2.0 m/s | 2.4 |
| 3.0 m/s | 3.1 |
Indicative U-values for oil tanks
| Position | ΔT | Unlagged | Lagged |
|---|---|---|---|
| Sheltered | up to 10°C | 6.8 | 1.7 |
| Sheltered | up to 27°C | 7.4 | 1.8 |
| Sheltered | up to 38°C | 8.0 | 2.0 |
| Exposed | up to 10°C | 8.0 | 2.0 |
| Exposed | up to 27°C | 8.5 | 2.1 |
| Exposed | up to 38°C | 9.1 | 2.3 |
| Underground | any temperature | 6.8 | — |
U-values are in W/(m²·°C).
Heat loss from exposed liquid surfaces
In an open tank, surface heat loss may be the largest heat-loss component. It depends mainly on surface temperature, air velocity and exposed surface area.
Worked example
- tank dimensions 3 × 3 × 2 m,
- 2/3 full,
- 12,000 kg liquid,
- liquid cp = 3.9 kJ/(kg·°C),
- 8°C → 60°C in 2 hours,
- 15 mm mild-steel vessel,
- 500 kg steel article every 20 minutes.
Start-up load
| Component | Load |
|---|---|
| Liquid heating | 338 kW |
| Vessel heating | 14 kW |
| Side losses | 7 kW |
| Surface losses | 9 kW |
| Total | 368 kW |
Operating load
| Component | Load |
|---|---|
| Side losses | 14 kW |
| Surface losses | 27 kW |
| Immersed article | 11 kW |
| Total | 52 kW |
Why start-up duty is higher
During start-up, both the liquid and vessel must absorb sensible heat. Once operating temperature has been reached, demand mainly consists of environmental losses and heat absorbed by cold material entering the process.
Warm-up time
A longer permitted warm-up period reduces the required mean heat-transfer rate, levels boiler demand and reduces instantaneous demand on the temperature-control system.
Practical calculation sequence
- Define tank geometry and fill level.
- Determine liquid mass and cp.
- Determine vessel mass and cp.
- Define initial and operating temperatures.
- Define warm-up time.
- Calculate liquid and vessel heating duties.
- Calculate solid-surface losses.
- Calculate exposed-liquid-surface losses.
- Add cold-material loads.
- Check start-up and operating duties separately.
Once heat demand is known, the heating method may be selected, including internal coils, jackets or a suitable heat exchanger. The actual loads should also be considered when selecting control valves and steam-trapping and condensate equipment.
Conclusion
Total tank duty is the sum of heating energy and the significant real heat losses. Insulation, air movement, exposed liquid surface and cold articles can all materially affect demand.
Start-up and operating loads should be calculated separately because they may differ by several times.
Frequently Asked Questions
What are the main components of tank heat load?
Liquid heating, vessel heating, solid-surface losses, exposed-liquid-surface losses and cold-material heating.
How is liquid heating duty calculated?
Using Q̇ = m·cp·ΔT/t.
How are wall heat losses calculated?
Using Q̇ = U·A·ΔT.
How does insulation affect heat loss?
It reduces the overall U-value and therefore the heat loss.
Why do open tanks lose more heat?
Because heat is also lost directly from the exposed liquid surface.
Why does air movement increase heat loss?
Higher air velocity increases convective heat transfer from exposed surfaces.
Why is start-up duty higher?
Because both the liquid and the vessel must be heated from their initial temperature.
How does warm-up time affect heat input?
A longer warm-up period reduces the required mean heat-transfer rate.