B-Safety BR 071 085 ClassicLine – Safety Shower Arm for Body Decontamination
Wall-mounted safety shower arm with exposed piping, designed for installation in industrial environments where water supply and shower head must remain accessible for visual inspection and periodic testing. The assembly features a ¾" female water connection, 525 mm projection, and installation height of 2345 mm ±100 mm.
Technical Specifications
- Operating dynamic pressure: 1.5–3 bar
- Standard flow rate: 50 l/min
- Alternative variants: 75 l/min / 20 GPM and 110 l/min
- Materials: stainless steel (AISI 304), chemically resistant plastic (POM)
- Colour coding: green / black
- Shower head: POM, self-draining
- Flow regulator: POM
Construction and Materials
The wall flange is manufactured from AISI 304 stainless steel with a green chemically resistant coating and includes four mounting holes. The ¾" shower arm is also AISI 304 with identical coating. The shower head is constructed from chemically resistant POM. Self-draining is provided between the valve and head, as required for installations per DIN EN 15154-1:2006.
Hydraulic Selection
The integrated automatic flow regulator maintains the specified spray pattern within the 1.5–3 bar dynamic pressure range. Flow rate variants correspond to hazard class I (50 l/min), hazard class II (75 l/min), and hazard class III (110 l/min) per DIN EN 15154-5:2019.
Standards and Accessories
Complies with DIN EN 15154-1:2006, DIN EN 15154-5:2019, ANSI Z358.1-2014, DIN 1988, DIN EN 1717, DIN-DVGW / DVGW NW-0417CL0263, and GOST-R. Supplied with body shower signage per EN ISO 7010 / ASR A1.3, PVC 150 × 150 mm, 15 m recognition distance. Optional accessories include IP65 flow switches, EX zone 1 & 2 versions, and 230 V / 50 Hz alarm system.
Application and Use Cases
- Industrial process areas with chemical exposure risk
- Facilities requiring compliance with DIN EN and ANSI safety shower standards
- Suitable for water as the process medium
- Recommended for locations where visual inspection and periodic functional testing are required
Description
Certification