Experience a new standard of industrial safety with the Bi-directional in-line deflagration flame arrester, short-time burning proof - H 41.0 N | KITO Armaturen. Built for high-performance and reliability, this flame arrester ensures ultimate protection against flame propagation in both directions of your pipeline system. Specially engineered for short-time burning resistance, it safeguards your operations from the risks of deflagration, offering peace of mind where it matters most.

Features & Benefits of the Bi-directional in-line deflagration flame arrester, short-time burning proof - H 41.0 N | KITO Armaturen

  • Bi-directional Safety: Effectively stops flames traveling in either direction, providing comprehensive pipeline protection and reducing the risk of fire spreading.
  • Short-Time Burning Proof: Designed to withstand temporary exposure to flames, maintaining its performance even in challenging situations and ensuring extra safety during unexpected incidents.
  • Rugged Industrial Design: Built from tough, corrosion-resistant materials for long-lasting performance in demanding industrial environments.
  • Easy Integration: Compact and straightforward to install, this arrester can be quickly retrofitted or added to new systems without disruption.
  • Low Maintenance: Engineered for durability and simple upkeep, supporting trouble-free operation and lower maintenance costs.
  • Reliable Certification: Meets strict international safety standards to guarantee optimal performance and compliance.

The Bi-directional in-line deflagration flame arrester, short-time burning proof - H 41.0 N | KITO Armaturen is an essential solution for industrial setups where flammable gases and vapors are handled. It acts as a trusted barrier, stopping flames if an ignition occurs and preventing the fire from spreading through pipework. Even if a flame from an explosion enters the line, the arrester’s advanced design extinguishes it instantly.

With its bi-directional capability, there’s no need to worry about the flow direction or pipeline layout. The device works equally well regardless of pressure or direction, ensuring your entire system stays protected. The short-time burning proof feature means the device continues to safeguard your plant, even if it comes into contact with flames for a brief period – adding an extra layer of security.

Choose the Bi-directional in-line deflagration flame arrester, short-time burning proof - H 41.0 N | KITO Armaturen for peace of mind, compliance with safety regulations, and protection you can count on every day.

Standard (Options)
  • DIN
Connection (Options)
  • Flanged
Material (Options)
  • 1.4571
  • Steel
Pressure Rating (Options)
  • PN 16
  • PN 40

Datasheet and documents

Description

KITO® RG-Def-IIA-…-1.2

KITO® RG-Def-IIA-…-1.2-T (-TT)

– design with flange connection –

  • For installation into pipes to the protection of vessels and components against deflagration of flammable liquids and gases.
  • Approved for all substances of explosion groups IIA1 to IIA with a maximum experimental safe gap (MESG) > 0.9 mm.
  • Bi-directionally working in pipes, whereby an operating pressure of 1.2 bar abs. and an operating temperature of 60 °C must not be exceeded.
  • The distance between a potential ignition source and the flame arrester must not exceed 50 times the inner pipe diameter.
  • All sizes are tested against “stabilized burning” and withstand this up to a max. burn time BT ≤ 30.0 min.
  • To detect a “stabilized burning” a thermocouple must be installed at each endangered side.
  • Mounting is acceptable in any position, in horizontal as well as in vertical pipes.