Miyawaki ER110 – Inverted Bucket Steam Trap

The Miyawaki ER110 is an inverted bucket steam trap made from cast iron FC250, designed for medium to large condensate loads in low to medium pressure steam systems. It operates on a mechanical steam-condensate separation principle using a U-shaped duct and bucket, without requiring electric or pneumatic actuators.

Technical Specifications

  • Connection: Flanged FF or RF.
  • Sizes: DN15–DN50 / 1/2"–2".
  • Flanges: ASME/JPI 150 lb, 300 lb, DIN PN16, JIS 10K / 16K / 20K.
  • Body Material: Cast iron FC250.
  • ER110-5: PMO / Δp max 0.5 MPa.
  • ER110-12: PMO / Δp max 1.2 MPa.
  • PMA: 1.2 MPa.
  • TMA / TMO: 220 °C.
  • PED 2014/68/EU, Article 4, Section 3, without CE marking.

Operation and Selection

The ER110 features a small vent hole at the top of the bucket for the removal of hot air and non-condensable gases, minimizing air locking. The series supports condensate recovery with backpressure up to 90% of upstream pressure, provided the return line has proper check and isolation valves.

Typical Applications

Suitable for heat exchangers, dryers, unit heaters, cleaning processes, dyeing, food/beverage, HVAC, and general industrial steam drainage. Selection is based on condensate load, available Δp, backpressure, temperature, DN, and flange standard.

Installation and Maintenance

Install in horizontal flow with the nameplate on top and follow the body arrow direction. The steam trap should be lower than the condensate-producing equipment; if not feasible, a lift fitting is required. Perform blow-off of the line before startup and allow maintenance space of over 180 mm.

FAQ

When to choose over ER105?
When higher flow or operation up to 1.2 MPa is required.

What to check for reduced discharge?
Blocked screen, debris in piston/pilot valve and seat, blocked vent hole, or operation above model's PMO.

Standard (Options)
  • DIN
  • ANSI
  • JIS
Connection (Options)
  • Flanged
Material (Options)
  • Cast Iron
Pressure Rating (Options)
  • PN 16
  • 0,5 - 1,2 Mpa

Description

1978 Received the Award for Excellence in Energy Saving

Features

Complete steam containment

A double steam separation mechanism (implemented with a U-shaped duct and inverted bucket) provides reliable steam separation and ensures trap tightness.

Free from steam and air locking

This model is free from steam and air locking due to a small air vent hole in the top of the bucket (discharges hot air and non-condensable gases).

Easy maintenance

For quick and easy maintenance, this model can be repaired directly in line.

Superb durability

Offers superb durability thanks to the SCCV System valve and robust super lever, as well as stainless steel internal components.

Condensate recovery

With its high degree of back pressure tolerance, this model supports condensate recovery at pressures up to 90% of the upstream pressure.

SuperDischargerSCCV_color_eng

*’SCCV System’ is an abbreviation of Self Closing and Centering Valve System.

Typical applications

Suitable for use in a wide range of fields including the plant industry, foodstuff manufacturing, dyeing, cleaning, and air conditioning.

Dimensions/Weight

ER110_FF
SizeDimensions (mm)Dimensions (in)Weight
LH1H2WLH1H2W(kg)(lb)
1/2”254200140120107.95.54.716,135.5
3/4”
1”
1 1/4”28021013011.08.35.118,139.9
1 1/2”
2”

Specifications

ModelConnection

Max. operating

pressure

Max. operating

pressure differential

Max. operating

temperature

Body material
TypeSize(MPa)(psig)(MPa)(psig)(℃)(℉)
ER110-5

Flanged

FF,RF*

1/2”0,5730,573220428

Cast iron

FC250

3/4”
1”
1 1/4”
1 1/2”
2”
ER110-121/2”1,21741,2174
3/4”
1”
1 1/4”
1 1/2”
2”

*Available flange standards: ASME/JPI 150lb, 300lb, DIN PN16, JIS 10K, 16K, 20K