Safety Shower Valve B-Safety BR 022 995

Wall-mounted activation valve for emergency safety showers, designed for exposed piping. Features a stainless steel ball valve and manual pull rod actuator. The unit can be installed on either side of the access point to maintain visible and immediate operability.

Technical Specifications

  • Water connection: Rp ¾” female
  • Operating pressure: 1–5 bar
  • Flow rate: ≥60 l/min at 1 bar dynamic pressure
  • Opening angle: 90°
  • Operation: non-self-closing (manual reset required)
  • Dimensions: 700 × 172 × 80 mm
  • Pull rod with ring handle: length 700 mm
  • Handle lower edge height: 0–1750 mm above floor, per applicable standards

Construction Materials

BR 022 995 is manufactured from polished stainless steel. Technical documentation specifies AISI 316 for valve body, ball, lever, clevis, pull rod, and rod support. The “OPEN” indicator plate is orange, photoluminescent plastic (DIN 67510).

Applications

Intended for fixed emergency showers in industrial environments with risk of exposure to chemicals, hot liquids, or contaminated media. Suitable for potable or process water in personnel safety installations.

Standards and Installation

Complies with DIN EN 15154-1:2006, DIN EN 15154-5:2019, ANSI Z358.1-2014, and GOST-R. For DIN EN 15154-1 compliance, the pipe section between valve and shower head must be self-draining.

Variant Comparison: BR 022 995 vs BR 022 985

BR 022 995 features AISI 316 stainless steel components and polished finish for enhanced material compatibility in corrosive or frequently washed industrial settings.

FAQ

Does the valve close automatically?
No. Manual reset is required; valve remains open until manually closed.

What should be verified before procurement?
Available pressure, flow ≥60 l/min, handle height, installation side, and self-draining requirement for piping.

Datasheet and documents

Description

Technical Specifications

  • Material: stainless steel
  • Surface: polished
  • Dimensions (H x W x D): 700 x 172 x 80 mm
  • Operating pressure: 1 to 5 bar
  • Flow rate: at least 60 l/min at 1 bar flow pressure
  • Water inlet: ¾“ female

Norms / Approvals

  • EN 15154-2:2006
  • EN 15154-5:2019
  • ANSI Z358.1-2014
  • GOST-R, Certificate-No. 0615463 0615463

Product description

The rod operated safety shower valve consists of a robust ball valve with drinking water approval, which can be mounted either to the right or left of the door. The volume flow is at least 60 liters / minute at 1 bar flow pressure. An additional holder ensures positioning of the pull rod.

Mounting-Instructions:

For an installation in accordance with EN 15154-1:2006 it must be ensured, that the safety shower installation is self-draining between valve and shower head.

DVGW
ISO9001_D_72

Technical Description

  • ball valve with pull rod actuation on wall flange of stainless steel, can be mounted either on the right or left side of the door, DIN-DVGW tested and certificated, water inlet ¾” female
  • flow rate at least 60 l/min at 1 bar flow pressure
  • pull rod with ring handle made of stainless steel, polished, length 700 mm
  • holder for pull rod made of stainless steel, polished
  • opening angle 90°, not self-closing
  • information sign “OPEN” for confusion-free use in an emergency, orange, photoluminescent according to DIN 67510
  • mounting height for lower edge of pull rod handle according to the standards listed below: 0 to 1750 mm height above floor
  • according to BGI/GUV-I 850-0, DIN 1988 and DIN EN 1717
  • according to ANSI Z358.1-2014, DIN EN 15154-1:2006  and DIN EN 15154-5:2019

Certification

DVGW    ISO9001_D_72