Pump trap - PPT14 | ADCA Valsteam ADCA - 1
Pump trap - PPT14 | ADCA Valsteam ADCA - 1

Pump trap - PPT14 | ADCA

ADCA ADCAMat PPT14 Pump-Trap

The PPT14 is an automatic pump-trap designed for condensate drainage in heat exchangers, heating coils, heated vessels, and steam units where stall conditions may occur. It combines a float steam trap and a pressure pump in one unit: when sufficient differential pressure is present, it operates as a steam trap, while when steam pressure falls below backpressure, the pumping function is activated using external motive steam.

Technical Specifications

  • Sizes: DN 40 x 25 and DN 50 x 40
  • Connections: EN 1092-1 PN 16, ASME B16.5 Class 150, ISO 7 Rp via threaded flanges
  • Variants: PPT14S in carbon steel, PPT14SS in stainless steel
  • Motive Medium: saturated steam
  • Motive Steam Pressure: 1–10 bar
  • Operating Temperature: 0–185°C
  • Pump Displacement: approximately 11 L per cycle
  • Fluids: steam condensate with specific gravity 0.8–1
  • CE Marking per PED for Group 2, PN 16, Category 2

Performance and Sizing

In pump mode, with a filling head of 300 mm, capacity depends on motive steam pressure and total backpressure. Selection tables indicate up to 1830 kg/h for DN 50 x 40 at low backpressure. In trap mode, capacity reaches up to 6200 kg/h for DN 40 x 25 and up to 10100 kg/h for DN 50 x 40, depending on differential pressure.

Materials and Sealing

Internal operating parts are stainless steel, springs are Inconel, and gaskets are stainless/graphite. Inlet and outlet check valves are A351 CF8M / 1.4408. These components are critical for wear, sealing, and repairability in hot condensate networks.

Applications

  • Exchangers with variable thermal load
  • Steam networks with high or variable return backpressure
  • Installations where condensate retention must be avoided
  • Closed-loop applications and vacuum conditions, with proper venting and receiver arrangement

FAQ

When is PPT14 chosen over a simple steam trap?
When load and control pressure create a stall possibility and the steam trap cannot always evacuate the condensate.

Does it require electrical power?
No. The pumping function is driven by saturated motive steam.

Standard (Options)
  • DIN
  • ANSI
Connection (Options)
  • Flanged
Material (Options)
  • Carbon Steel
  • Stainless Steel
Pressure Rating (Options)
  • PN 16

Datasheet and documents

Description

MATERIAL

Carbon steel and stainless steel

SIZES

11/2” x 1” and 2” x 11/2”
DN 40 x 25 and DN 50 x 40

CONNECTIONS

Flanged EN 1092-1 PN 16
Flanged ASME B16.5 Class 150
Female threaded ISO 7 Rp