Ceiling-Mounted Emergency Safety Shower B-Safety BR 085 085 ClassicLine
Ceiling-mounted emergency body shower with exposed piping and ¾" female water inlet. This configuration is specified where hydraulic supply is routed from above and visible, inspectable piping is required for maintenance or periodic inspection. Installation height is 2445 mm ±100 mm, with a free headroom of 245 mm.
Technical Specifications
- Operating pressure range: 1.5–3 bar (dynamic)
- Standard flow rate: 50 l/min
- Alternative flow rates: 75 l/min / 20 GPM and 110 l/min
- Pull rod with ring: 700 mm
- Shower head: POM, black, self-draining
- Signage: PVC 150 × 150 mm, EN ISO 7010 / ASR A1.3, 15 m recognition distance
Construction Materials
Ceiling flange, piping, and arm are AISI 304 stainless steel with green chemically resistant coating. Pull rod is AISI 201. The ¾" ball valve is DZR brass CW724R, suitable for dezincification resistance in hydraulic networks. Flow regulator is POM.
Operation and Flow Selection
Integrated flow regulator ensures stable spray pattern within 1.5–3 bar. 50 l/min version corresponds to hazard class I per EN 15154-5:2019, 75 l/min to class II, and 110 l/min to class III.
Standards and Accessories
Technical documentation references EN 15154-1:2006, EN 15154-5:2019, ANSI Z358.1-2014, DIN 1988, EN 1717, and DIN-DVGW / DVGW NW-0416CL0425. Available options: floor activation cable, 1150 mm pull rod, service shut-off ¾", thermostatic mixing 20–43 °C, IP65 flow switch, EX zone 1 & 2 switch, 230 V / 50 Hz alarm.
Applications and Use Cases
- Industrial process areas with overhead water supply
- Chemical handling zones requiring visible, inspectable piping
- Facilities with periodic maintenance and inspection protocols
- Suitable for potable and process water
FAQ
- What is the recommended installation height? 2445 mm ±100 mm.
- Which standards are met? EN 15154-1, EN 15154-5, ANSI Z358.1, DIN 1988, EN 1717.
- What are the flow rate options? 50, 75, and 110 l/min, selectable by variant.
- What media are compatible? Water, including potable and process water.
Description