Variable body safety shower for installation in suspended ceilings - PremiumLine - BR 089 095 / V | B-Safety
B-Safety BR 089 095 / V PremiumLine
Adjustable emergency body shower for suspended ceiling or false ceiling installation. Constructed from stainless steel, with ¾" female water supply connection. The “V” version refers to installation geometry adaptation, not manual flow adjustment. Overall width: 285–1535 mm; headroom: 360–1610 mm, depending on project dimensions.
Technical Specifications
- Operating dynamic pressure: 1.5–3 bar
- Nominal flow rate: 50 l/min
- Available variants: 75 l/min / 20 GPM and 110 l/min
- Shower head lower edge: 2200 mm ±100 mm from finished floor
- Pull rod: adjustable length 710–2040 mm
- Connection via adapter with integrated flow regulator
Construction Materials
- Shower head: stainless steel AISI 316
- ¾" ball valve: AISI 316
- Piping: AISI 316
- Pull rod with ring: AISI 316
- Double nipple: AISI 316
- Connection adapter and ceiling flange: AISI 304
- Flow regulator: POM
The self-draining shower head minimizes water retention after activation or testing, reducing stagnant water zones above the ceiling and supporting maintenance in hard water networks.
Flow Rate Variants
- BR 089 095 / V: 50 l/min, hazard class I
- BR 089 095 / V75L: 75 l/min / 20 GPM, hazard class II
- BR 089 095 / V110L: 110 l/min, hazard class III
Selection should be based on risk assessment, available dynamic pressure, pressure drop to the shower, and chemical exposure in the area.
Standards and Accessories
Complies with EN 15154-2:2006, EN 15154-5:2019, ANSI Z358.1-2014, DIN 1988, EN 1717, and DIN-DVGW / DVGW NW-0417CL0263. Accessories: ¾" isolation valve, thermostatic mixing 20–43°C, IP65 flow switch, EX zone 1 & 2 switch, 230 V / 50 Hz alarm.
Applications and Media
Suitable for chemical plants, laboratories, and industrial facilities requiring emergency decontamination. Compatible with potable and process water. Not designed for steam or aggressive media. Maintenance should include periodic activation and inspection for scaling or leakage.